DC Reactor (Smoothing Reactor) Technical Summary
Core Functions
Harmonic Suppression: Limits AC ripple (20–150Hz) on the DC side (typical ≤10% of rated current).
Power Factor Improvement: Increases input PF from 0.75 to 0.95 (50Hz operation).
Current Continuity: Maintains minimum critical current to prevent rectifier discontinuity.
Key Specifications
Inductance: 1–30 mH (varies with inverter power rating)
Current Rating: 100–3000 A
Voltage Drop: <2% of rated voltage
Application Scenarios
Class A (Mandatory Installation):
Grid THDv >5% or short-circuit capacity >40× inverter rating
Multi-inverter parallel systems (≥3 units)
Class B (Recommended Installation):
Transformer capacity >10× inverter rating (impedance <4%)
Voltage imbalance rate: 1.8–3%
Class C (Optional Installation):
Systems with reactive power compensation (anti-resonance required)
Long cable feeds (>100 m)
Installation Guidelines
Distance to inverter: <5 m (to minimize line inductance effects)
Spacing from capacitors: ≥3× device length
Must be optimized for IGBT switching frequency (typically 2–8 kHz)
Protection Features
Built-in temperature sensors (85°C alarm, 105°C trip)
Insulation class: F (155°C)
Sizing Formula:L min =( 2π⋅f⋅ΔIΔU)⋅K(ΔU: allowable ripple voltage, f: ripple frequency, ΔI: allowable ripple current, K: safety factor 1.2–1.5)
Performance Benefits:
Reduces input harmonic current by 40–60%
Decreases capacitor thermal losses by 15–25%
Complies with IEEE 519-2014 standards for harmonic mitigation.